SE-134C Series - Ground-Fault Ground-Check Monitor

External overview image
Roll Over to Zoom
The SE-134C/SE-135 is a microprocessor-based, combination ground-wire monitor and ground-fault relay for resistance-grounded or solidly grounded systems. It continuously monitors the integrity of the ground conductor to protect portable equipment from hazardous voltages caused by ground faults. The SE-134C/SE-135 is field proven in monitoring trailing cables on large mobile equipment such as drag-lines, mining shovels, shore-to-ship power cables, dock-side cranes, stacker-reclaimers, submersible pumps, and portable conveyors.

FEATURES

BENEFITS

Adjustable pickup
(0.5 - 12.5 A)

Unit can be used on a wide variety of trailing cable applications

Adjustable time delay
(1 - 2.5 s)

Adjustable trip delay for quick protection and system coordination

Output contacts

Separate annunciation of ground-fault and ground-check faults

Ground-check
LED indication

Indication of open or short ground-check wire makes it easier to find faults

CT-Loop monitoring

Alarms when CT is not connected

High-induced-ac rejection

Makes unit suitable for applications with high voltages and long cables

DFT (Harmonic) filter

Prevents false operation

Zener-characteristic termination assembly

Provides reliable ground-check loop verification

Fail-safe circuits

Ensures ground-check and ground-fault circuits remain safe even in the event of equipment failure

Conformal coating

Additional coating protects circuit boards against harsh environment

Access specifications, certifications, check availability and order parts below

Catalog #Supply
Voltage
VAC
Supply
Voltage
VDC
Relay Contacts ConfigIEEE Device NumbersRelay
Contact
Operating
Weight (lbs/g)Auto Manual ResetConformally coatedCT Loop MonitoringFrequencyGF Trip Level AGF Trip Time sHarmonic FilteringReset TypeSystem typeStockCompare
SE-134C-00120 - 240120 - 2401 Form A (N.O.); 1 Form B (N.C.); 2 Form C (N.O./N.C.)3GC - 50G - 50N - 51G - 51NFail-safe / Non Fail-safe0 KgLatching; AutoresetStandardStandard50; 60; ASD0.50 - 12.50.10 - 2.5Standard (DFT)Front-panel switch/Remote N.O. ContactResistance Grounded AC
SE-134C-1024 - 481 Form A (N.O.); 1 Form B (N.C.); 2 Form C (N.O./N.C.)3GC - 50G - 50N - 51G - 51NFail-safe / Non Fail-safe0 KgLatching; AutoresetStandardStandard50; 60; ASD0.50 - 12.50.10 - 2.5Standard (DFT)Front-panel switch/Remote N.O. ContactResistance Grounded AC
SE-134C-XGC-00120 - 240120 - 2401 Form A (N.O.); 1 Form B (N.C.); 2 Form C (N.O./N.C.)3GC - 50G - 50N - 51G - 51NFail-safe / Non Fail-safe0 KgLatching; AutoresetStandardStandard50; 60; ASD0.50 - 12.50.10 - 2.5Standard (DFT)Front-panel switch/Remote N.O. ContactResistance Grounded ACCheck
SE-134C-XGC-1024 - 481 Form A (N.O.); 1 Form B (N.C.); 2 Form C (N.O./N.C.)3GC - 50G - 50N - 51G - 51NFail-safe / Non Fail-safe0 KgLatching; AutoresetStandardStandard50; 60; ASD0.50 - 12.50.10 - 2.5Standard (DFT)Front-panel switch/Remote N.O. ContactResistance Grounded ACCheck

  • Showing 9 items
Part # Part Description RoHS Pb-free RoHS (2015/ 863/EU) Certificate REACH (SVHC’s) Declaration Halogen Free REACH (SVHC’s)
SE-134C-00 Ground-Fault Ground-Check Mon RoHS No 05/30/2017 PbFree No 05/30/2017 CoC_RoHS9_SE-134C-00_05-12-2021 REACH201_Declaration_(Contain)_SE-134C-00_05-12-2021
Contains
SE-134C-10 GFGC MONITOR LOW VOLTAGE RoHS No 02/04/2020 PbFree No 02/04/2020 CoC_RoHS9_SE-134C-10_02-05-2020 Yes
02/04/2020
If the product environmental information that you are looking for does not appear in this tab,